Best Fuse Selection Tips for Motor Starters
In a medium-voltage motor starter, start from the fuse the starter manufacturer specifies, then confirm voltage, R rating, barrel count and mounting. Give the supplier the motor's starting current, starting time and starts per hour, check that the overload relay and contactor cover currents below the fuse's minimum interrupting rating, and replace fuses as a matched set.
About this list
These tips apply to medium-voltage motor circuits protected by R-rated current-limiting fuses, with a note on IEC motor-circuit fuse-links. Each one is tied to ANSI/IEEE C37.46, IEC 60644, or a manufacturer's published catalog or technical guide, and figures are attributed to the source that gives them. The list helps you prepare a correct request; it does not size a fuse.
1. Start from the fuse the starter manufacturer specifies
In short: Every new installation and every replacement
A medium-voltage combination starter is designed and tested as a system: contactor, overload relay and fuse. Mersen's catalog states that the motor starter manufacturer generally specifies the R-rated fuse size, and that R-rated fuses must be coordinated with overload relays in combination motor starters.
Record the starter make, model and nameplate, and the full part number printed on the existing fuse, before you order anything. Those two pieces of information answer most replacement questions.
2. Read the R number as a melting point, not an ampere rating
In short: Avoiding wrong-size orders
ANSI/IEEE C37.46 defines an R-rated fuse as one that melts in 15 to 35 seconds at 100 times its R number. A 9R fuse, for example, melts in that window at 900 A. The fuse's continuous current rating is a separate number that the manufacturer publishes for each R rating.
Mersen's catalog adds that the continuous ampere rating reflects the fuse's thermal capability and should not be the sole factor in selection. Order by R number, voltage and part number together.
3. Collect starting current, starting time and starts per hour
In short: Motors with long acceleration times or frequent starts
A motor fuse has to survive every start without its element being gradually weakened. ABB's medium-voltage fuse technical guide notes that direct-on-line starting current may be up to eight times rated current, and its selection method for IEC motor fuse-links reads the fuse rating from charts for starting times of 6, 15 and 60 seconds and from the number of starts per hour.
Even for R-rated fuses, these three figures are what a supplier needs to confirm that a proposed fuse will not melt or age during normal starts. IEC 60644 formalizes the same concern for IEC motor-circuit fuse-links by setting requirements for withstanding motor starting pulses.
4. Make sure the relay and contactor cover what the fuse cannot
In short: Checking an existing protection scheme
R-rated fuses are back-up fuses. Under ANSI C37.40, a back-up fuse interrupts only down to a stated minimum interrupting current. Below that, it cannot be relied on to clear.
Littelfuse's R-rated page describes the division of duty: the controller's overload relays provide overload and locked-rotor protection, and the controller interrupts low-value short circuits within its own capability, which protects the fuse from sustained overcurrents below its minimum interrupting rating. If a relay setting has been changed or a relay replaced, the fuse selection should be reviewed with it.
5. Tell the supplier when the motor is on a soft starter
In short: Reduced-voltage and soft-start installations
ABB's technical guide notes that soft starting equipment based on power electronics can significantly limit inrush current, and that soft-start motors can then be protected by a fuse-link with a much lower rated current.
That cuts both ways: a fuse chosen for direct-on-line starting may be larger than the soft starter's own protection requires, and a fuse chosen for soft starting may not survive if the motor is later switched to across-the-line starting in a bypass arrangement. Give the supplier the starter model and its bypass arrangement, not just the motor size. DENCO's R-rated family covers motor and soft-starter fuses.
6. Match voltage, barrel count and mounting
In short: Replacements in existing starters
R-rated fuses come in single, double and triple barrel constructions, in ferrule styles for spring clips and bolt-in styles, some with hookeye attachments. Mersen, for example, publishes ferrule, bolt-on and DIN-dimension R-rated ranges, and Eaton lists R-rated fuses specific to its AMPGARD starters.
A fuse that fits the clips is not necessarily correct. Check the voltage rating, clip centers, barrel diameter and any indicator or striker that the starter uses to signal an open fuse.
7. Replace fuses as a matched set after a fault
In short: Post-fault maintenance
ABB's technical guide, citing IEC 60282-1, suggests replacing all three fuse-links in a three-phase circuit even if only one or two have operated, unless it is certain that no fault current passed through the others. Current that did not open a fuse can still change its characteristics.
The same guide advises against mixing fuse types, classes or manufacturers within one three-phase set, even when the rating plates match.
8. Do not mix IEC motor fuse-links with R-rated fuses
In short: Plants with both North American and IEC-built switchgear
IEC motor-circuit fuse-links are specified to IEC 60644 and IEC 60282-1 and do not carry an R rating. Some manufacturers offer R-rated fuses in DIN dimensions, but a DIN-size fuse is not automatically R-rated, and an R-rated fuse is not automatically suitable for an IEC starter.
Treat a change between the two systems as a new selection, with the starter manufacturer's approval.
What to send with a quote request
For a medium-voltage motor starter fuse, DENCO needs:
- Existing fuse part number and manufacturer, if replacing
- Starter make, model and nameplate data, and whether it is a soft starter
- System voltage
- Motor full-load current, starting current, starting time and starts per hour
- Barrel count, mounting style and any indicator or striker requirement
- Quantity and required-by date (DENCO quotes a 30-day lead time on all products)
Frequently asked questions
Can I size an R-rated fuse from motor full-load current alone?
No. The R number is a melting point, not an ampere rating, and the fuse has to be checked against starting current, starting time, starts per hour and the starter's overload relay and contactor. Follow the starter manufacturer's specification.
Why do my motor fuses open during starts with no fault?
Common reasons are a fuse chosen for a shorter starting time or fewer starts than the motor now sees, a change from soft starting to across-the-line starting, or fuses weakened by an earlier fault and not replaced as a set. Have the selection reviewed before fitting a larger fuse.
Does DENCO make fuses for soft starters?
Yes. DENCO's R-rated family covers medium-voltage motor and soft-starter fuses in single, double and triple barrel construction. Send the starter details and the existing part number, and DENCO engineering will confirm the right part.
Is an R-rated fuse enough to protect the motor?
No. It provides short-circuit protection only. Overload and locked-rotor protection come from the starter's overload relay.
Limits of this article
- This article is educational. It is not a protection coordination study and does not produce a final fuse selection.
- Fuse selection must be confirmed against the motor starter manufacturer's data and a coordination study.
- Figures from ABB and other manufacturers describe their products and methods; use the data for the specific fuse and starter you install.
- Working inside medium-voltage motor starters requires qualified personnel, NFPA 70E PPE and lockout; confirm that capacitors and bypass circuits are de-energized.
Related
- Best R-Rated Motor Fuse Manufacturers
- E-Rated vs R-Rated Fuses: 7 Key Differences
- R-rated motor and soft-starter fuses
- Medium-voltage fuse selection guide
- Request a quote
Sources
- IEEE C37.46-2010, Standard Specifications for High-Voltage (>1000 V) Expulsion and Current-Limiting Power Class Fuses (IEEE Xplore record)
- IEEE C37.40-2003, Standard Service Conditions and Definitions for High-Voltage Fuses (IEEE Xplore record)
- IEC 60644:2009+AMD1:2019, High-voltage fuse-links for motor circuit applications (IEC webstore)
- IEC 60282-1:2020, High-voltage fuses, Part 1: Current-limiting fuses (IEC webstore)
- ABB, Medium-voltage fuses Technical guide (Distribution Solutions)
- Mersen, Medium Voltage Fuses catalog (MV section, 2018)
- Littelfuse, R-Rated Series medium-voltage fuses
- Eaton, Bussmann series Medium voltage ANSI/IEEE R-Rated fuses