DENCO FusesRequest a quote

Loadbreak Elbow & Load Break Disconnect Fuses

DENCO loadbreak elbow fuses are current-limiting fuses built into a fused elbow for 25kV class underground distribution, with a load break disconnect variant. The element is silver in a silica sand fill within a fiberglass body.

Request a quoteCross-reference a partCall +1 (305) 273-6226

Specifications

Loadbreak Elbow & Load Break Disconnect Fuses — ratings and scope
ParameterValue
Nominal system voltage25kV class (AC)
Nominal fuse voltage15.5kV maximum (AC)
Ampere rating20A
Interrupting rating50kA
ConstructionFiberglass tube body, silver-plated terminals, silver (Ag) element, star tube, silica sand H31, brass bushing
Published curvesTime-current curve, I2t correction curve and watts-loss correction curve

Applications

  • 25kV class underground distribution
  • Fused elbow terminations
  • Load break disconnect duty

Limits and boundaries

  • Single published rating (20A at 15.5kV) -- confirm availability of other ratings with DENCO
  • Elbow and disconnect variants differ; confirm which is required

Standards and testing

  • Tested to CESI-IPH test report Nr. 23152130449.0258

Wording reflects the evidence DENCO holds. “Designed to” a standard is not the same as certified or listed to it; where a certification exists we publish the certificate number.

Technical documents

Data sheets, dimensional drawings and time-current curves for this family are available on request. Ask for the documents you need.

What we need to quote

Voltage and whether the system is AC or DC, continuous current, required interrupting rating, physical dimensions and mounting, any indicator requirement, and the standard or approval you must meet. A photograph or drawing of the existing part is usually the fastest route.

Technical review

Specifications on this page are quoted from DENCO’s product catalog. Confirm any rating against DENCO engineering before specifying.

Request a quote for Loadbreak Elbow & Load Break Disconnect Fuses