Capacitor fuse guide · Specify and buy
23 kV Capacitor Fuses (DNX23 and DNXC23)
A 23 kV capacitor fuse protects capacitor units rated 19920 V and 21600 V, the units used in wye banks on 34.5 kV (34500Y/19920 V) systems and in the series groups of substation banks. DENCO offers the clip-style DNX23 (3C to 40C and 50C to 140C) and the full-range DNXC23 at 12, 18 and 25 A. Units of 15125, 20800, 22130 and 22800 V need DENCO's confirmation.
Key points
- 19920 V and 21600 V units map to 23 kV in every published unit fuse table used in this guide. 22800 V units appear in only one table.
- On a 34.5 kV wye system each unit sees 34.5 / 1.732 = 19.92 kV, which is why 19920 V units are the workhorse of this class.
- Substation banks stack 19.92 kV and 21.6 kV units in series groups; a relay maker's 138 kV example uses four groups of 21.6 kV units.
- DNXC23 stops at 25 A. A 400 kvar, 19920 V unit already needs 27.1 A after a 1.35 margin.
- DENCO's DNXC catalog p.74 derates above 25 °C at 0.0065 per °C, which matters with only three DNXC23 ratings to choose from.
From 34.5 kV systems and series groups to 23 kV fuses
The 23 kV class is the top DNXC voltage and the usual class for the highest-voltage distribution capacitor units. A full-range current-limiting table, an outdoor combination table and an indoor combination table all assign 19920 V and 21600 V units to 23.0 kV fuses. The outdoor combination table also lists 22800 V units at 23.0 kV.
The direct route is a wye bank on a 34.5 kV system. ANSI C84.1 nominal voltages, as adopted by one state regulator, include 34500 V and 34500Y/19920 V, and one capacitor maker's table pairs a 19920 V unit with a 34.5 kV wye system. One maker's pole racks for single-phase units are built for systems from 2,400 V to 34,500 V, so 19.92 kV pole banks are a catalog item.
The other route is the substation. Banks at transmission voltages are built from parallel groups connected in series to reach the system voltage, and one relay maker notes that choosing the highest available unit voltage results in the fewest series groups and the greatest sensitivity for unbalance protection. One relay maker's worked example is a 138 kV ungrounded single wye bank with four series groups of fourteen 21.6 kV units, where each unit runs at 138 / (1.732 x 4) = 19.92 kV in normal service. A regional transmission guideline describes 230 kV banks with 200 kvar, 19.92 kV units.
| Unit voltage | Typical use | Full-range table | Outdoor combination | Indoor combination |
|---|---|---|---|---|
| 15125 V | 26.2 kV wye system (one maker's table) | Not listed | Not listed | Not listed |
| 19920 V | 34500Y/19920 V wye; substation series groups | 23.0 kV | 23.0 kV | 23.0 kV |
| 20800 V | Catalogued unit voltage | Not listed | Not listed | Not listed |
| 21600 V | Substation series groups | 23.0 kV | 23.0 kV | 23.0 kV |
| 22130 V | Catalogued unit voltage | Not listed | Not listed | Not listed |
| 22800 V | Catalogued unit voltage | Not listed | 23.0 kV | Not listed |
Units between the tables
One capacitor maker catalogs standard unit voltages of 15125 V, 19920 V, 20800 V, 21600 V, 22130 V and 22800 V, all at 150 kV BIL with a single bushing. The published fuse tables cover only some of them. 15125 V sits above the 14400 V top of the 15.5 kV lists and below the 19920 V start of the 23 kV lists. 20800 V and 22130 V appear in none of the three tables, and 22800 V appears in one.
The voltage arithmetic is worth having before you call. IEEE's 2005 interpretation of IEEE 18-2002 says fuses should withstand the 110% contingency that units ride through. 1.1 x 19920 V is 21,912 V. 1.1 x 21600 V is 23,760 V, and 1.1 x 22800 V is 25,080 V, both above 23,000 V. One maker's indoor table lists its 23.0 kV class with a rated maximum of 25.3 kV, 110% of the class figure. For 15125 V units, 1.1 x 15125 V is 16,638 V, above 15.5 kV. These are numbers, not answers: DENCO engineering states the class for any unit not in the tables.
DNX23 and DNXC23 catalog numbers
DENCO's DNX23, catalog p.72, is a clip-style current-limiting capacitor fuse with threaded end studs available, listed in two C ranges. Its DNXC23, catalog p.74, is a full-range current-limiting capacitor fuse for bus bar to lead mounting with three ampere ratings. The DNXC catalog states the series was tested at IPH to IEC 60282-1: 2009-10 and IEC 60282-2: 2008-04; that is the catalog's wording, quoted as such.
The DNX C number is defined in DENCO's catalog by melting: 1000 seconds at 1.7 to 2.4 times the C number. No standard defines C ratings for capacitor fuses.
| Series | Catalog numbers | Range | Interrupting rating | Mounting |
|---|---|---|---|---|
| DNX23 | DNX23-3C - 40C | 3C to 40C | 50 kA asymmetrical | Clip style |
| DNX23 | DNX23-50C - 140C | 50C to 140C | 50 kA asymmetrical | Clip style |
| DNXC23 | DNXC23-12, DNXC23-18, DNXC23-25 | 12 A, 18 A, 25 A | 50 kA | Bus bar to lead |
Unit current for 19920 V, 21600 V and 22800 V units
Current per unit is kvar divided by unit kV. Published guides for current-limiting unit fuses then apply a 1.35 protective margin, which one maker ties to normal overvoltages, harmonics, capacitor tolerances and a 25 °C ambient. At these voltages the currents are small: a 200 kvar, 19920 V unit draws about 10 A.
The table runs to 600 kvar because capacitor makers catalog units that large at these voltages; one maker lists standard and heavy duty units from 100 to 600 kvar. Each cell reads unit current / current x 1.35.
| Unit kvar | 19920 V | 21600 V | 22800 V |
|---|---|---|---|
| 100 | 5.0 / 6.8 A | 4.6 / 6.3 A | 4.4 / 5.9 A |
| 150 | 7.5 / 10.2 A | 6.9 / 9.4 A | 6.6 / 8.9 A |
| 200 | 10.0 / 13.6 A | 9.3 / 12.5 A | 8.8 / 11.8 A |
| 300 | 15.1 / 20.3 A | 13.9 / 18.8 A | 13.2 / 17.8 A |
| 400 | 20.1 / 27.1 A | 18.5 / 25.0 A | 17.5 / 23.7 A |
| 500 | 25.1 / 33.9 A | 23.1 / 31.2 A | 21.9 / 29.6 A |
| 600 | 30.1 / 40.7 A | 27.8 / 37.5 A | 26.3 / 35.5 A |
Worked examples with only three DNXC23 ratings
With 12, 18 and 25 A to choose from, small changes in kvar or ambient move the answer a whole size, or off the list. DENCO's DNXC catalog p.74 derates above 25 °C: A_T = A_25 x [1 - 0.0065 x (T - 25)], where T is the maximum ambient the fuse will see. The factor is 0.9025 at 40 °C and 0.805 at 55 °C, so DNXC23-12 carries 10.8 A and 9.7 A, DNXC23-18 carries 16.2 A and 14.5 A, and DNXC23-25 carries 22.6 A and 20.1 A.
200 kvar, 19920 V: 13.6 A required. DNXC23-12 is too small at any ambient. DNXC23-18 covers it at 25 °C, at 40 °C and at 55 °C (14.5 A).
300 kvar, 19920 V: 20.3 A required. DNXC23-25 covers it at 25 °C and at 40 °C (22.6 A). At 55 °C it carries 20.1 A, just short, and there is no larger DNXC23. Take it to DENCO.
400 kvar, 21600 V: the arithmetic lands exactly on 25.0 A. DNXC23-25 matches only at a 25 °C ambient; any derating puts it below. A 400 kvar, 19920 V unit needs 27.1 A, beyond the DNXC23 list at any temperature, which points the conversation at the DNX23 50C to 140C range or another arrangement.
Substation banks: margins and stored energy
Not every user applies 1.35. A regional transmission guideline multiplies overvoltage 1.1, tolerance 1.15 and harmonics 1.1 for switching devices, then recommends 1.25 rather than the 1.35 sum, and builds its unit fuse table on 1.25. A relay maker's coordination procedure likewise calls for a fusing ratio of 1.25 or less for individual unit fuses. If your company standard uses a different margin, tell DENCO which one.
Stored energy grows with the group. The same transmission guideline notes that in a 230 kV bank with eighteen 200 kvar units per group, a failed unit and its fuse see the energy of the other 17 units, approximately 3.15 MVAR. It suggests generally keeping effective parallel capacitance under 4,650 kvar, about 15,000 watt-seconds, to stay within expulsion fuse energy withstand and keep can rupture probability low. DENCO does not publish a DNXC parallel energy limit; send the group size.
Group size also drives unbalance protection. In the relay maker's 138 kV example, with 14 units per group the bank can tolerate two failed units in a group but not three before healthy units exceed their permissible overvoltage. Unit fuses remove the failed units; the unbalance relay counts them.
The order of operations matters as much as the ratings. A relay maker's handbook, citing IEEE C37.99-2000, says unbalance protection should coordinate with the individual unit fuses so that the fuses isolate a faulty unit before the protection trips the whole bank, with the alarm level chosen to pick up the first blown fuse. One unbalance relay maker factory-sets a 10-second lockout delay so unit fuses can respond to evolving faults and the failed units can be identified by eye. Ask DENCO for the DNX23 or DNXC23 time-current curves so your relay settings can be checked against them.
Fused, fuseless or unfused near 34.5 kV
34.5 kV is roughly where bank designs change. One relay maker's paper says fuseless designs are not usually applied below about 34.5 kV, because they need more than 10 elements in series, and that unfused designs are normally used on banks below 34.5 kV where series strings are not practical, or on higher voltage banks with modest parallel energy. That is one paper's view, not a standard, but it explains why 23 kV class unit fuses show up both on 34.5 kV distribution banks and on externally fused transmission banks.
Fault current at a failed unit depends on the arrangement. One manufacturer's guide says faults in ungrounded or multi-series-group banks are capacitively limited, typically to less than two or three times bank load current. DENCO prints 50 kA for the DNXC and 50 kA asymmetrical for the DNX.
Quote checklist for 23 kV capacitor fuses
- Unit voltage and kvar, and the unit data sheet if the voltage is 15125, 20800, 22130 or 22800 V.
- Bank voltage, connection, number of series groups and units per group.
- The fusing margin your standard uses (1.35, 1.25 or other).
- Available fault current and maximum ambient at the fuse.
- DNX23 clip mounting or DNXC23 bus bar to lead mounting, indicator option, quantity.
- Part number of any fuse being replaced, so DENCO engineering can confirm a replacement.
Common mistakes at 23 kV
- Choosing the class from the 34.5 kV system voltage. Each unit in a 34.5 kV wye bank sees 19.92 kV.
- Assuming every unit above 19 kV fits 23 kV. 21600 V and 22800 V units exceed 23 kV at 110%, and three catalogued voltages are in no table.
- Expecting a DNXC23 above 25 A. The list is 12, 18 and 25 A.
- Ignoring derating because the currents look small. With three ratings, one size step is the whole margin.
- Applying 1.35 when the owner's standard uses 1.25, or the reverse, without saying so in the request.
Frequently asked questions
What fuse for a 19.92 kV capacitor?
A 19920 V unit takes a 23 kV fuse in every published table used here. With DENCO parts that is the DNX23 or DNXC23. A 200 kvar unit needs 13.6 A after a 1.35 margin, which points to DNXC23-18.
What fuse for a 34.5 kV capacitor bank?
In a 34500Y/19920 V wye bank each unit sees 19.92 kV, so the unit fuses are 23 kV class. A fuse that must withstand full 34.5 kV line-to-line voltage is a different question; see the 27 kV and 38 kV page and ask DENCO.
What are the DNXC23 ratings?
DNXC23-12, DNXC23-18 and DNXC23-25: 12, 18 and 25 A at 23 kV, full-range current-limiting, bus bar to lead mounting, 50 kA interrupting rating.
What fuse for a 21.6 kV capacitor?
Published tables put 21600 V units in the 23 kV class. 1.1 x 21600 V is 23,760 V, so ask DENCO to confirm how its 23 kV rating covers that contingency. A 300 kvar unit needs 18.8 A after a 1.35 margin.
What fuse for a 22.8 kV capacitor unit?
Only one published table lists 22800 V units, at 23.0 kV. The 110% contingency is 25,080 V. Send DENCO the unit data and let DENCO engineering confirm the class.
What fuse for a 15125 V capacitor?
15125 V units fall between the 15.5 kV and 23 kV lists in the published tables, and 110% of 15125 V is 16,638 V. DENCO needs the unit data to state the class.
DNX23 or DNXC23?
The DNX23 is clip style, listed by C range from 3C to 140C. The DNXC23 is full-range for bus bar to lead mounting at 12, 18 or 25 A. Large units above about 25 A of required current point to the DNX23 conversation.
Next step
Limits of this article
- Currents, margins, derated ratings and part numbers here are calculated starting points, not a recommendation. Confirm with the capacitor maker's data and case rupture curve, a protection study and DENCO engineering, including outrush I2t and parallel energy.
- Class assignments come from published manufacturer tables, which do not cover every catalogued unit voltage. None is a standard.
- Capacitors hold a charge. Disconnect, wait at least 5 minutes, short circuit each unit between all terminals and the case or rack, and bond ungrounded racks to ground per OSHA 29 CFR 1910.269(w)(1); follow NFPA 70E.
- Dimensions, weights and any DNXC parallel energy limit are not stated. DENCO's family-level specifications are pending technical review by DENCO.
Related
- 15.5 kV Capacitor Fuses (DNX15 and DNXC15)
- 27 kV and 38 kV Capacitor Fuses
- DNXC Selection by Capacitor kvar and Unit Voltage
- Capacitor Fuse Voltage Rating: Unit Voltage, System Voltage and Connection
- Fusing Substation Capacitor Banks: Externally Fused, Internally Fused and Fuseless
- DNX and DNXC current-limiting capacitor fuses
- DNX vs DNXC: Which DENCO Capacitor Fuse Fits?
- How to Read a DNX or DNXC Catalog Number
- Replacing Blown Capacitor Fuses Safely
- All capacitor fuse guides
Sources
- DENCO Fuses catalog, DNX and DNXC current-limiting capacitor fuses, pp.72 to 74
- IEEE Standards Interpretations for IEEE Std 18-2002 (May 2005)
- North Carolina Utilities Commission Rule R8-17 (ANSI C84.1 nominal voltages)
- PJM TSS guideline V.G, PJM Design and Application of Shunt Capacitors (2017)
- Published manufacturer capacitor fuse selection guides, capacitor unit and rack catalogs, and relay maker protection papers (unbalance calculations, bank fundamentals)
- OSHA 29 CFR 1910.269(w)(1)
- NFPA 70E, Standard for Electrical Safety in the Workplace