Capacitor fuse guide · Choose
Capacitor Fuse Interrupting Rating and Parallel Stored Energy
A capacitor fuse faces two energy sources when a unit fails: fault current from the power system and the energy stored in the healthy units in parallel with the failed one. The interrupting rating must cover the available fault current on the same basis, and the fuse and failed unit together must handle the parallel energy without rupturing the case.
Key points
- Whether a fault is limited by the system or by the capacitors depends on the bank connection and grounding.
- Energy stored at 1.1 times crest voltage works out to E = 1.21 x kvar x 1000 / (2 pi f), about 3.21 J per kvar at 60 Hz. One manufacturer's guide uses 3.19 J per kvar.
- Published parallel-energy limits of 10, 15, 20, 30 and 50 kJ come from different sources and apply to different things. Attribute each and do not merge them.
- Compare interrupting ratings on the same basis. Symmetrical and asymmetrical figures are not interchangeable.
- When group energy is too high, the published remedies are more series groups, splitting the bank, or current-limiting fuses.
Two sources of fault energy
When a capacitor unit fails short, current flows into it from two places. The power system supplies fault current at power frequency, and the healthy units in the same parallel group discharge their stored energy into the failed unit at high frequency. A fuse has to deal with both, and the two checks are different: the first is the interrupting rating, the second is energy.
One manufacturer's capacitor fuse selection guide puts the energy problem directly: when a capacitor fails, the energy stored in its series group of capacitors is available to dump into the combination of the failed capacitor and fuse, and the failed capacitor and fuse must be able to absorb or hold off this energy with a low probability of case rupture.
How the bank connection sets the fault current
The same guide explains that in ungrounded banks, or banks with more than one series group, faults are capacitively limited and the available fault current is typically less than two or three times the capacitor bank load current. In single series group grounded wye or delta banks, faults are inductively limited and the current is limited only by the available system fault current. The second case is where the interrupting rating decides.
Worked example. A 600 kvar pole bank of three 200 kvar, 7,200 V units draws 200 / 7.2 = 27.8 A per phase; USDA RUS Bulletin 1724D-112 gives about 28 A for a 600 kvar bank at 7,200 V. One manufacturer's pole bank fusing guide says operating ungrounded wye limits fault current to about three times line current, here about 3 x 27.8 = 83 A. Connect the same bank grounded wye at a point with several thousand amperes available and the fuse must interrupt the full system fault current.
High available fault current also brings case rupture into play. One capacitor maker's pole bank guide lists the largest expulsion links that coordinate with its tank rupture curves, 100K and 65T, and the fault currents up to which they do. Above those values it points to current-limiting fuses, ungrounded wye operation or moving the rack. A municipal utility standard states the same limit in its own words: fusing greater than 100K is not allowed because of the capacitor tank rupture curve.
| Circuit X/R | Standard and heavy-duty units | Extreme-duty units |
|---|---|---|
| 0 | 10,000 A | 15,000 A |
| 5 | 7,800 A | 11,700 A |
| 10 | 6,900 A | 10,350 A |
| 15 | 6,500 A | 9,750 A |
Interrupting rating: compare like with like
The interrupting rating is the highest fault current the fuse is rated to clear at its rated voltage. Check it against the maximum available fault current at the bank, including future system growth if your utility publishes it.
Ratings are printed on different bases. The tutorial presented with IEEE C37.48.1-2002 notes that the instantaneous crest of a symmetrical fault is 1.414 times the rms symmetrical value, and that the crest of a fully asymmetrical fault may be double that, about 2.8 times, depending on circuit X/R. DENCO's catalog prints its DNX rating as 50kA asymmetrical and its 1 kV to 5.5 kV Types in kA symmetrical. Do not convert one to the other without the X/R data and the test basis; ask DENCO which basis applies.
Fuse type changes the numbers sharply. One manufacturer publishes its expulsion capacitor fuses at 7,400 A symmetrical (10,000 A asymmetrical) in its 9.7 kV class, 3,600 A (5,000 A) at 16.6 kV and 1,800 A (2,500 A) at 26.2 kV, while its current-limiting capacitor fuse classes are rated 40 to 90 kA symmetrical for inductive faults. That gap is one reason current-limiting fuses are used where fault current is high.
| DENCO series | Voltage | Interrupting rating as printed |
|---|---|---|
| Types 1, 2 and 5 | 1.5 kV | 40kA sym |
| Types 3 and 4 | 1 kV to 1.5 kV | 40kA to 50kA sym |
| Types 1, 3 and 5; Types 1, 2 and 6 | 2.5 kV; 3 kV | 50kA sym |
| Types 7, 8 and 9 | 4.3 kV and 5.5 kV | 65kA sym |
| DNX | 2.8 kV to 38 kV | 50kA asymmetrical |
| DNXC | 8.3 kV to 23 kV | 50kA |
Calculating parallel stored energy
A capacitor stores E = 0.5 C V^2. Writing the capacitance in terms of kvar, C = kvar x 1000 / (2 pi f V^2), and charging it to 1.1 times the crest of rated voltage, V = 1.1 x 1.414 x Vrated, the voltage terms cancel and the energy per kvar is fixed by frequency alone: E = 1.21 x kvar x 1000 / (2 pi f).
At 60 Hz that is 1.21 x 1000 / 377 = 3.21 J per kvar. At 1.2 times crest it is 1.44 x 1000 / 377 = 3.82 J per kvar, and at 50 Hz, 1.1 times crest, 1.21 x 1000 / 314.2 = 3.85 J per kvar. One manufacturer's selection guide uses 3.19 J per kvar at 10% overvoltage and 3.80 J per kvar at 20%; its base constant of 2.64 is slightly below the exact 2.653, and the difference is about 0.6%.
The energy that matters is the energy of the units that can discharge into the failed one, normally the other units in its parallel group. A PJM guideline adds that adjacent banks on a common bus add energy. In fuseless banks, a relay maker's paper notes, the discharge energy is small because no capacitor units are connected directly in parallel.
Worked examples: energy in a parallel group
One manufacturer's guide works this example: a bank of 5 series groups, each of 10 x 200 kvar units at 13,280 V. A failed unit's fuse sees the energy of the other nine units, 3.19 x 9 x 200 = 5,742 J, which that guide finds suitable for its 15 kV expulsion fuse.
The table extends the same arithmetic to larger groups. The last row is above every published expulsion figure quoted in the next section and is a case for current-limiting fuses or a different bank arrangement.
| Group | kvar that can discharge | At 3.19 J/kvar | At 3.21 J/kvar |
|---|---|---|---|
| 10 x 200 kvar | 9 x 200 = 1,800 kvar | 5,742 J | 5,778 J |
| 14 x 300 kvar | 13 x 300 = 3,900 kvar | 12,441 J | 12,519 J |
| 16 x 400 kvar | 15 x 400 = 6,000 kvar | 19,140 J | 19,260 J |
| 25 x 400 kvar | 24 x 400 = 9,600 kvar | 30,624 J | 30,816 J |
Published parallel-energy limits
Several limits appear in the literature. They come from different sources and apply to different things, so cite each on its own. Converted at 3.19 J per kvar, 10 kJ is about 3,135 kvar, 15 kJ about 4,700 kvar and 50 kJ about 15,670 kvar.
DENCO's catalog data used for this guide does not list a parallel-energy capability for DNX or DNXC fuses. If your group energy is high, send the kvar per unit and the number of units in parallel, and DENCO engineering will confirm the application.
- Bank design rule: a published protection paper recommends keeping a parallel group's stored energy below 15 kJ for all-film dielectric or 10 kJ for all-paper or paper-film dielectric, at peak maximum voltage, in externally fused banks.
- Utility guideline: PJM says generally less than 4,650 kvar of effective capacitance at nominal voltage (15,000 watt-seconds) should be connected in parallel, and notes that 6,300 kvar in parallel has been used successfully since 1993 with standard expulsion fuses.
- Expulsion fuse tubes: one maker rates its capacitor expulsion fuse tubes at 20 kJ (50 A tubes) or 30 kJ (80 A tubes) of parallel energy when used with the unit spacing recommended per IEEE Std 18-2012.
- Expulsion application: another maker's guide says its expulsion fuse is not normally applied above 20 kJ, equivalent to 6,000 kvar, because of case rupture, and applies current-limiting fuses above that.
- Current-limiting fuses: one maker publishes its full-range current-limiting capacitor fuse as safely fusing at least 50 kJ; another lists maximum parallel discharge energy for its current-limiting classes of 85, 77, 75, 88 and 50 kJ at 2.8, 5.5, 8.3, 15.5 and 23 kV.
How the fuse type changes the energy split
In an expulsion fuse the link melts, the arc generates gas from the tube lining, and the fuse conducts until a natural current zero. One selection guide notes that most of the parallel energy is then absorbed in the failed capacitor. A back-voltage current-limiting fuse absorbs a large portion of the energy itself, and the same guide says a current-chopping design leaves trapped voltage on the other units.
A current-limiting fuse also caps the power-system current. One manufacturer's catalog gives an example: on an 8.3 kV circuit with 20,000 A rms symmetrical available and an unlimited peak of 48,000 A, a 40 A current-limiting fuse lets through 7,800 A peak. What still reaches the failed unit is the fuse's total clearing I2t, which is also its let-through I2t.
Compare that with the capacitor's withstand. One capacitor maker prints a minimum of 2,000,000 A2s on its standard and heavy-duty tank rupture curves for fault currents of 10,000 A or less, rising to 5,600,000 A2s up to 15,000 A for extreme-duty units. At 10,000 A, 2,000,000 A2s corresponds to 2,000,000 / 10,000^2 = 0.02 s, about 1.2 cycles at 60 Hz.
When energy is too high, the remedies in a relay maker's paper are more series groups, splitting the bank into a double wye, or current-limiting fuses. That paper suggests the split when a group's parallel kvar rises above about 4,650 kvar.
Common mistakes
These errors show up in interrupting and energy checks.
- Comparing an asymmetrical rating with a symmetrical fault study figure, or the reverse.
- Checking interrupting rating against the capacitively limited fault current when the bank is a single series group grounded wye that sees full system fault current.
- Counting only the units in one bank when an adjacent bank on the same bus adds energy.
- Merging limits from different sources, for example applying a fuse maker's 20 kJ figure as if it were a bank design rule.
- Assuming a larger expulsion link adds safety margin when available fault current is already above the level at which it coordinates with the tank rupture curve.
- Forgetting future growth in system fault current at the bank location.
Frequently asked questions
Is a 50kA rating enough for my capacitor bank?
Only if the maximum available fault current at the bank, on the same symmetrical or asymmetrical basis, is below it. Capacitively limited banks typically see less than two or three times load current; single series group grounded wye or delta banks can see the full system fault level.
How do I calculate parallel energy in a capacitor bank?
Add the kvar of the units that can discharge into a failed unit, normally the rest of its parallel group, and multiply by the energy per kvar: about 3.21 J at 60 Hz and 1.1 times crest voltage, or 3.19 J in one manufacturer's guide. Nine 200 kvar units give about 5.7 kJ.
Do I count the failed unit in the parallel energy?
Published wording refers to the energy stored in the failed unit's group that can dump into the failed capacitor and fuse. In practice that is the other units in the parallel group. Follow the method of the source whose limit you are applying.
Is the 20 kJ limit a standard?
No. It is one manufacturer's application limit for its own expulsion capacitor fuse. The 15 kJ and 10 kJ figures are a bank design recommendation from a published protection paper, and 4,650 kvar is PJM's guideline. None is an IEEE or IEC requirement.
Why is the joules per kvar figure 3.19 in one guide and 3.21 here?
Both come from charging the parallel capacitance to 1.1 times crest of rated voltage. The exact 60 Hz arithmetic gives 3.21 J per kvar; the manufacturer's guide uses a base constant of 2.64 that rounds it to 3.19. The 0.6% difference does not change a selection.
Does DENCO publish a parallel energy rating for DNX or DNXC?
Not in the catalog data used for this guide. Send the kvar per unit, the number of units per parallel group, the unit voltage and the bank connection, and DENCO engineering will confirm whether the fuse suits the energy.
What does DENCO need to check interrupting duty?
Available fault current with its basis (symmetrical or asymmetrical) and X/R if known, system and unit voltage, bank connection and grounding, kvar per unit, units in parallel, and any adjacent banks on the same bus.
Next step
Limits of this article
- This article is general guidance, not a protection study. Confirm every fuse selection, and every worked example here, with the capacitor maker's data and a protection study by a qualified engineer.
- Capacitors hold a charge after they are disconnected. Before handling fuses or units, disconnect, wait, short circuit and ground as OSHA 29 CFR 1910.269(w)(1) requires, and follow NFPA 70E, Standard for Electrical Safety in the Workplace.
- Parallel-energy figures are manufacturer, utility or paper-specific limits for their own products or design methods. They are not standard requirements and must not be combined.
- Symmetrical and asymmetrical interrupting ratings are not converted in this article. Confirm the test basis with DENCO.
- DENCO ratings quoted here are from DENCO's catalog and are pending technical review. Confirm current part numbers and ratings with DENCO engineering before ordering.
Related
- Capacitor Fuse I2t: Melting, Clearing, Outrush and Parallel Energy, With Worked Numbers
- Capacitor Case Rupture and How Fusing Prevents It
- Fusing Substation Capacitor Banks: Externally Fused, Internally Fused and Fuseless
- Current-Limiting vs Expulsion Capacitor Fuses
- DNX and DNXC capacitor fuses
- C-rated capacitor fuses
- How to Size a Capacitor Fuse
- Capacitor Fuse Voltage Rating: Unit Voltage, System Voltage and Connection
- Full-Range vs Back-Up Current-Limiting Capacitor Fuses
- All capacitor fuse guides
Sources
- ABB Inc., Capacitor fuses, Technical selection guide, 1VAG38852-TG Rev A (2024)
- ABB Power T&D, Capacitor Fuses Selection Guide, TD 38-852 (1999)
- USDA Rural Utilities Service, Bulletin 1724D-112, The Application of Capacitors on Rural Electric Systems
- PJM TSS guideline V.G, PJM Design and Application of Shunt Capacitors (2017)
- City of Columbus Division of Power, TDMIS 2700 Protection (2022)
- Eaton TD230005EN, Group capacitor fusing for pole-mounted capacitor banks (2017)
- Eaton R230-91-1 and R230-91-2, tank rupture TCCs for MV single-phase capacitors
- Eaton CA132034EN, Capacitor expulsion fuse (2023)
- Eaton Cooper Power series, NXC full-range current-limiting capacitor fuse, Catalog Data CA132047EN (2019)
- Eaton Cooper Power series, NX indoor current-limiting fuses, Catalog Data CA132049EN (2020)
- Samineni, Labuschagne, Pope, Principles of Shunt Capacitor Bank Application and Protection (SEL)
- Brunello, Kasztenny, Wester, Shunt Capacitor Bank Fundamentals and Protection (GE Multilin, 2003)
- Presenting IEEE C37.48.1-2002, IEEE Switchgear Committee WG on Full Range Fuses (2003)
- DENCO Fuses catalog, C-rated capacitor protection fuses, pp.59-75 (DNX / DNXC pp.72-74)
