E-Rated Transformer Protection Fuses
DENCO E-rated fuses provide primary protection for distribution transformers on medium-voltage systems. They are current-limiting, supplied in the 9F60/EJ-1, 9F62/EJO-1 and Clip Lock 14 series, with or without a visual trip indicator or microswitch, in clip-on, bolt-on, clip-lock and custom mountings.
Request a quoteCross-reference a partCall +1 (305) 273-6226
Specifications
| Parameter | Value |
|---|---|
| AC voltages | 625V, 1500V, 2.75kV, 5.5kV, 8.25kV, 12kV, 15.5kV, 24kV, 25.8kV, 36kV (AC) |
| Ampere range | 0.5E to 400E (0.5A to 400A) |
| Interrupting ratings | 31kA, 38kA, 50kA, 60kA, 63kA, 80kA, 82kA, 100kA, 120kA |
| Indicator options | With or without visual trip indicator or microswitch |
| Mounting | Clip-on, bolt-on with brackets, clip-lock, or custom mounting designs |
| Type references | 9F60, 9F62 Series, EJ-1, EJO-1 and Standard |
| General purpose vs power distribution | General-purpose current-limiting fuses are defined by IEEE Std C37.40-2003; the catalog lists power distribution fuses separately as pre-dating that definition |
Catalog numbers
| Catalog no. | Availability | Last reviewed |
|---|---|---|
| DCCB-1E | Active | 2026-08-27 |
| DCCB-2E | Active | 2026-08-27 |
| DCCB-3E | Active | 2026-08-27 |
| DCCB-5E | Active | 2026-08-27 |
| DCCB-7E | Active | 2026-08-27 |
| DCCB-10E | Active | 2026-08-27 |
| DCCB-15E | Active | 2026-08-27 |
| DCCB-20E | Active | 2026-08-27 |
| DCCB-25E | Active | 2026-08-27 |
| DECB-30E | Active | 2026-08-27 |
| DECB-40E | Active | 2026-08-27 |
| DECB-50E | Active | 2026-08-27 |
| DECB-65E | Active | 2026-08-27 |
| DECB-80E | Active | 2026-08-27 |
| DECB-100E | Active | 2026-08-27 |
| DGCB-125E | Active | 2026-08-27 |
| DGCB-150E | Active | 2026-08-27 |
| DGCB-200E | Active | 2026-08-27 |
| DCEB-1E | Active | 2026-08-27 |
| DCEB-2E | Active | 2026-08-27 |
| DCEB-3E | Active | 2026-08-27 |
| DCEB-5E | Active | 2026-08-27 |
| DCEB-7E | Active | 2026-08-27 |
| DCEB-10E | Active | 2026-08-27 |
| DCEB-15E | Active | 2026-08-27 |
| DCEB-20E | Active | 2026-08-27 |
| DCEB-25E | Active | 2026-08-27 |
| DDJB-1E | Active | 2026-08-27 |
| DDJB-2E | Active | 2026-08-27 |
| DDJB-3E | Active | 2026-08-27 |
| DDJB-5E | Active | 2026-08-27 |
| DDJB-7E | Active | 2026-08-27 |
| DDJB-10E | Active | 2026-08-27 |
| DDJB-15E | Active | 2026-08-27 |
| DDJB-20E | Active | 2026-08-27 |
| DDJB-25E | Active | 2026-08-27 |
| DFJB-30E | Active | 2026-08-27 |
| DFJB-40E | Active | 2026-08-27 |
| DFJB-50E | Active | 2026-08-27 |
| DFJB-65E | Active | 2026-08-27 |
Full list renders once DENCO confirms per-part availability (Q2).
Applications
- General purpose transformer protection
- Power distribution fuse duty
- Main and back-up protection designs
- Indoor or outdoor within an enclosure
Limits and boundaries
- Enclosure required for outdoor installation
- Final selection requires DENCO engineering review
Standards and testing
- Designed to ANSI C37
Wording reflects the evidence DENCO holds. “Designed to” a standard is not the same as certified or listed to it; where a certification exists we publish the certificate number.
Technical documents
Data sheets, dimensional drawings and time-current curves for this family are available on request. Ask for the documents you need.
What we need to quote
Voltage and whether the system is AC or DC, continuous current, required interrupting rating, physical dimensions and mounting, any indicator requirement, and the standard or approval you must meet. A photograph or drawing of the existing part is usually the fastest route.
Common questions
What does the E in an E-rated fuse mean?
It is a melting characteristic defined by standard, not a manufacturer designation. Under ANSI/IEEE C37.46 an E-rated fuse of 100 A or below must melt within 300 seconds at an RMS current between 200% and 240% of its continuous current rating; above 100 A it must melt within 600 seconds at between 240% and 264%. Because the criterion is defined rather than proprietary, an E rating means the same thing whoever made the fuse.
Is an E-rated fuse full range, general purpose or back-up?
That is a separate question from the E rating, and ANSI C37.40 defines the three classes by how far down the current range the fuse can be relied on to interrupt. A full-range fuse interrupts any current that will melt its element. A general-purpose fuse interrupts down to the current that melts the element in one hour, so a lower overcurrent needs another device. A back-up fuse interrupts only down to a stated minimum interrupting current and must have a low-current device in series with it. Which class applies to a specific DENCO part is confirmed by DENCO against that part.
What is the difference between a current-limiting fuse and an expulsion fuse?
An expulsion fuse interrupts using the gases its own arc produces. It limits how long the overcurrent lasts but not how large the fault current becomes. A current-limiting fuse melts and abruptly introduces a high resistance, cutting both the magnitude and the duration of the current before interrupting it — but only while the current is inside its specified current-limiting range. Replacing an expulsion cutout link with a current-limiting design changes the let-through energy the rest of the installation sees, so it should be assessed rather than assumed.
Are E-rated fuses from different manufacturers interchangeable?
The E rating fixes the melting characteristic and nothing else. Voltage rating, interrupting rating, barrel count, overall length, clip or bolt centres, and any indicator or microswitch requirement all still have to match, and a fuse that physically fits is not necessarily electrically equivalent. Send us the part number or a photograph of the existing fuse and its mounting and we will confirm against it rather than answer from a table.
Technical review
Specifications on this page are quoted from DENCO’s product catalog. Confirm any rating against DENCO engineering before specifying.