5.5 kV Capacitor Fuses (DNX5)

A 5.5 kV capacitor fuse is the class two published manufacturer tables assign to 4160 V and 4800 V capacitor units, used in delta banks on 4160 V and 4800 V systems and in wye banks on 7200 V and 8320Y/4800 V systems. DENCO's 5.5 kV current-limiting capacitor fuse is the DNX5, listed as DNX5-6C - 18C and DNX5-20C - 75C. A full-range table uses 8.3 kV instead.

Key points

  • 4160 V and 4800 V units map to 5.5 kV in both an outdoor and an indoor published combination fuse table. A full-range table from another maker puts them at 8.3 kV.
  • The indoor table goes further and uses 5.5 kV for every unit from 2400 V to 4800 V.
  • 1.1 x 4800 V is 5280 V, inside 5.5 kV. One maker lists the 5.5 kV class with a 6.05 kV rated maximum.
  • DENCO's 5.5 kV options are the DNX5 (6C to 75C, clip style) and the Types 7, 8 and 9 (6 A to 75 A, 65 kA symmetrical).
  • Staged metal-enclosed banks are the common home for this class. Give DENCO the step size, reactor and switching details.

Unit voltages and systems that point to 5.5 kV

Two published tables from one fuse maker agree that 4160 V and 4800 V capacitor units take a 5.5 kV fuse: its outdoor combination current-limiting table and its indoor combination table. The indoor table also places 2400 V and 2770 V units in the 5.5 kV class. A full-range current-limiting table from a different maker, whose product line starts at 8.3 kV, puts all of those units in its 8.3 kV class.

Getting to a 4160 V or 4800 V unit depends on the bank connection. In a delta bank the units carry line-to-line voltage, so a 4160 V delta bank uses 4160 V units and a 4800 V delta bank uses 4800 V units. In a wye bank the units carry line-to-neutral voltage. One capacitor maker's table pairs a 4160 V unit with a 7200 V wye system and a 4800 V unit with an 8320 V wye system; 8320Y/4800 V appears on the ANSI C84.1 nominal list as adopted by one state regulator.

Routes to the 5.5 kV class. Fuse class columns are examples from published manufacturer tables.
System and connectionUnit voltageOutdoor combinationIndoor combinationFull-range
4160 V, delta bank4160 V5.5 kV5.5 kV8.3 kV
4800 V, delta bank4800 V5.5 kV5.5 kV8.3 kV
7200 V system, wye bank4160 V5.5 kV5.5 kV8.3 kV
8320Y/4800 V, wye bank4800 V5.5 kV5.5 kV8.3 kV
4160Y/2400 V, wye bank2400 V2.8 kV5.5 kV8.3 kV

Voltage margin inside the 5.5 kV class

IEEE's 2005 interpretation of IEEE 18-2002 says capacitor units should stay in service for contingencies up to 110% of rated voltage and that their fuses should withstand that overvoltage too. For the two units that define this class: 1.1 x 4160 V is 4576 V and 1.1 x 4800 V is 5280 V. Both sit under 5500 V.

One maker's indoor table also gives each class a rated maximum voltage of 110% of the class figure, referencing IEEE C37.40, which puts its 5.5 kV class at 6.05 kV. That is the published reason 4800 V units fit here comfortably, while at 4.3 kV the same 110% check on a 4160 V unit goes over the class. Ask DENCO to confirm the corresponding figure for the DNX5.

The class also covers wye banks with lower unit voltages in the indoor table, such as 2400 V units on a 4160Y/2400 V system. Another maker's low-voltage guidance prefers the nearest available fuse voltage so the voltage generated while the fuse interrupts does not stress the system. When the unit is well below the class, raise that with DENCO.

DNX5 and the other DENCO 5.5 kV fuses

DENCO's catalog p.72 lists the 5.5 kV DNX in two C ranges. It is a clip-style current-limiting capacitor fuse, with threaded end studs available and a listed body diameter that is a maximum. At the same voltage, DENCO's catalog p.70 lists capacitor protection fuse Types 7, 8 and 9, catalogued in amperes by maximum AC voltage.

The C number is DENCO's convention, since no standard defines a C rating. The catalog says the DNX melts in 1000 seconds at a current of 1.7 to 2.4 times its C number. DENCO maps your required current to a C number; the number itself is not a continuous ampere rating.

  • The DNXC is not offered at 5.5 kV. If a specification calls for a full-range, bus bar to lead fuse on 4160 V or 4800 V units, the DENCO DNXC option is the 8.3 kV class.
  • With or without a blown fuse indicator is a family-level option for DENCO C-rated fuses; state your choice.
DENCO 5.5 kV capacitor fuses as catalogued
SeriesListing as printedRangeInterrupting rating as printed
DNX (p.72)DNX5-6C - 18C6C to 18C50 kA asymmetrical (DNX series)
DNX (p.72)DNX5-20C - 75C20C to 75C50 kA asymmetrical (DNX series)
Types 7, 8 and 9 (p.70)5500 V AC6 A to 75 A65 kA symmetrical

Unit current at 4160 V and 4800 V

For a single-phase unit, current is kvar divided by unit kV. Published guides for medium voltage unit fuses add a 1.35 protective margin; one maker says it covers normal overvoltages, harmonics, capacitor tolerances and a 25 °C ambient, and its indoor fuse guide states the margin for a 40 °C ambient instead. The table below uses 1.35 as plain arithmetic.

One capacitor maker lists 200 kvar as its largest standard unit from 2400 V to 4800 V, so the table stops there.

Calculated: I = kvar / kV and I x 1.35. Not a fuse selection.
Unit kvar4160 V: current4160 V: x1.354800 V: current4800 V: x1.35
5012.0 A16.2 A10.4 A14.1 A
10024.0 A32.5 A20.8 A28.1 A
15036.1 A48.7 A31.3 A42.2 A
20048.1 A64.9 A41.7 A56.3 A

Worked example: 900 kvar on an 8320Y/4800 V system

A 900 kvar grounded wye bank on an 8320Y/4800 V system needs 300 kvar per phase. With 200 kvar as the largest standard 4800 V unit in one maker's catalog, a practical layout is two 150 kvar units in parallel per phase, each with its own fuse.

Each unit draws 150 / 4.8 = 31.3 A. With the 1.35 margin the fuse needs at least 42.2 A of continuous capability. Build the same 300 kvar per phase from three 100 kvar units and each fuse needs only 28.1 A, but there are three fuses per phase, and when one unit fails, two healthy units totaling 200 kvar discharge into it instead of one 150 kvar unit.

Compare a 600 kvar delta stage at 4160 V built from three 200 kvar units: 48.1 A per unit, 64.9 A with the margin. The delta stage needs a larger rating per fuse because each unit is larger and runs at a lower voltage. Both answers are starting points for DENCO, which checks them against the capacitor maker's case rupture curve and the inrush and outrush duty.

Staged metal-enclosed banks at 5 kV class

Much 5.5 kV fusing happens inside metal-enclosed capacitor banks. One bank maker builds them from 2.4 kV through 38 kV with up to 15 capacitor steps, fuses each capacitor individually with current-limiting fuses to improve bank reliability and protect against case rupture, and fits 44 uH transient inrush reactors per stage. It switches stages with vacuum contactors below 6.6 kV.

The makers differ on connection. One maker's manual says its 5 kV class banks are normally connected in delta, while another maker builds its metal-enclosed banks ungrounded wye as standard. The difference changes the unit voltage, so check the drawing rather than assuming.

Stage switching is where back-to-back inrush comes from. One switching maker describes back-to-back inrush as on the order of tens of kiloamperes and tens of kilohertz, which is why staged banks use reactors. A unit fuse must ride through that duty without operating, so send DENCO the step kvar, the reactor value and how often stages switch.

Heat in the enclosure

Enclosed fuses run warmer than the air outside. One bank maker's manual calls for shading where daytime temperatures exceed 40 °C and sets cabinet fans to turn on at about 85 °F. DENCO's catalog prints a temperature derating formula only for its DNXC series. For a DNX5 or a Type 7, 8 or 9 in an enclosure, tell DENCO the highest ambient the fuse will see and let DENCO check the rating.

Information DENCO needs for a 5.5 kV quote

  • Unit voltage (4160 V, 4800 V or lower) and kvar for each unit.
  • System voltage and connection, delta or wye, grounded or ungrounded.
  • Number of steps, kvar per step, units in parallel per phase, and inrush reactor value.
  • Available fault current at the bank bus.
  • Harmonic content or filter tuning.
  • Highest ambient inside the enclosure.
  • Clip mounting or threaded end studs, indicator option, quantity.
  • Part number of any fuse being replaced, so DENCO engineering can confirm a replacement.

Common mistakes at 5.5 kV

  • Assuming a specification for 8.3 kV full-range fuses on 4800 V units is an error. It follows a different maker's table; ask DENCO whether the DNX5 or a DNXC8 suits the bank.
  • Using the wye unit voltage on a delta drawing. A 4800 V delta bank uses 4800 V units, not 2770 V units.
  • Sizing for steady current only in a staged bank and ignoring back-to-back inrush between steps.
  • Mixing up the two DENCO 5.5 kV families. The DNX5 is listed by C range; the Types 7, 8 and 9 by amperes.
  • Leaving out the enclosure temperature. DNX derating is not printed, so DENCO needs the number to check it.

Frequently asked questions

What fuse for a 4800 V capacitor?

Two published tables from one fuse maker put 4800 V units in the 5.5 kV class. DENCO's 5.5 kV capacitor fuses are the DNX5 and the Types 7, 8 and 9. A full-range table from another maker uses 8.3 kV for the same unit.

5.5 kV capacitor fuse for a 4160 V capacitor?

Yes, published combination fuse tables assign 4160 V units to 5.5 kV, and the 110% contingency, 4576 V, stays inside the class. DENCO will confirm the DNX5 C number or Type rating from your kvar.

What size fuse for a 200 kvar 4.8 kV capacitor?

The unit draws 200 / 4.8 = 41.7 A, and 56.3 A with a 1.35 margin. That is the arithmetic starting point; DENCO sets the rating after checking the case rupture curve and inrush.

Is there a DNXC at 5.5 kV?

No. DENCO lists the DNXC at 8.3, 15.5 and 23 kV. At 5.5 kV the DENCO choices are the clip-style DNX5 and the Types 7, 8 and 9.

What is the maximum voltage of a 5.5 kV capacitor fuse?

One maker's indoor table lists 6.05 kV as the rated maximum for its 5.5 kV class, which is 110% of the class figure. DENCO catalogs its 5.5 kV Types at 5500 V AC; ask DENCO for the DNX5 maximum.

What fuses do 5 kV metal-enclosed capacitor banks use?

One bank maker fuses each capacitor individually with current-limiting fuses, with blown fuse indication and an inrush reactor per stage. With 4160 V or 4800 V units, that points to the 5.5 kV class; DENCO can quote from the bank data.

What does DNX5-20C - 75C mean?

It is the upper 5.5 kV DNX row: voltage digit 5 for the 5.5 kV class and a C range of 20C to 75C. Name the C number you need and DENCO confirms the part number.

Next step

Request a 5.5 kV capacitor fuse quote

Request a capacitor fuse quote See DNX and DNXC fuses

Limits of this article

  • Currents and margins here are calculated starting points, not a fuse selection. Confirm against the capacitor maker's data, the case rupture curve and a protection study, and with DENCO engineering.
  • Class assignments come from published manufacturer tables that disagree with each other. None is a standard.
  • Capacitors hold a charge. Disconnect, wait at least 5 minutes, short circuit and ground per OSHA 29 CFR 1910.269(w)(1), and follow NFPA 70E. Metal-enclosed bank manuals may require a longer wait before entry.
  • DNX dimensions, the DNX5 rated maximum voltage and any DNX derating are not stated here. DENCO's family-level specifications are pending technical review by DENCO.