Capacitor fuse guide · Specify and buy
Capacitor Fuse RFQ Checklist: What DENCO Needs to Quote
To quote a capacitor fuse, DENCO needs the capacitor unit voltage and kvar, the bank connection and grounding, the available fault current, the number of units in parallel, any harmonic or switching duty, the maximum enclosure ambient, the mounting style, and the quantity and date. If you are replacing a fuse, add its part number and photos.
Key points
- Send raw bank data, not only a target amp rating. Sizing margins differ by manufacturer and region, so DENCO checks the inputs.
- Unit voltage and kvar give the unit current (kvar / kV) and point to the fuse voltage class.
- Bank connection and fault current decide whether faults are limited by the capacitors or by the system.
- Units in parallel set the stored energy a failed unit and its fuse must absorb, about 3.19 J per kvar in one maker's method.
- Give the maximum ambient inside the enclosure. DNXC ratings drop to 80.5% at 55 °C under the DENCO catalog formula.
- Mounting photos, indicator choice, quantity, spares and test requirements complete the request.
Why a complete request saves a round trip
A capacitor fuse is sized against the capacitor, not against a load. The same 200 kvar unit can need different fuses depending on how the bank is connected, how much fault current is available, how many units sit in parallel and how hot the enclosure gets. If any of that is missing, the first reply to an RFQ is a list of questions.
The table below lists what to send and why each item matters. You do not need every row to start a conversation, but each missing row is something DENCO engineering has to ask about before a firm quote.
It also matters who is asking. A utility replacing fuses in a pole or substation bank, an OEM building metal-enclosed equipment, and a plant engineer adding power factor correction each hold different parts of the data. Send what you hold, name who holds the rest, such as the capacitor supplier or the engineer who owns the protection study, and DENCO engineering can ask the right person directly.
The checklist
Send as much of this as you have with your request.
| What to send | Why it matters |
|---|---|
| Existing fuse part number and maker, with photos of the label and mounting | Lets DENCO engineering confirm a replacement from the actual hardware. No cross-reference is assumed from a number alone. |
| Capacitor unit rated voltage and kvar, and the capacitor manufacturer | Unit current is kvar divided by kV. Unit voltage also drives the fuse voltage class. |
| System voltage and bank connection: grounded wye, ungrounded wye, double wye, H-bridge or delta; number of series groups | Connection changes the voltage across a fuse when it clears and whether fault current is limited by the capacitors or by the system. |
| Available fault current at the bank, and its basis (symmetrical or asymmetrical) and X/R | The fuse must interrupt it. DNX and DNXC are listed at 50 kA; the DNX value is stated as asymmetrical. |
| Number of units in parallel per series group, and any adjacent banks on the same bus | Sets the parallel stored energy that discharges into a failed unit and its fuse. |
| Harmonic content, or the filter tuning if the bank is a harmonic filter | Capacitors offer a low impedance path to harmonics, so more current flows through the fuse. |
| Switching arrangement: back-to-back banks, reactors, switching frequency | Inrush and outrush stress the fuse element without blowing it, and the fuse must withstand that duty. |
| Maximum ambient inside the enclosure | DNXC fuses are derated above 25 °C using the formula on DENCO catalog p.74. |
| Mounting: clip style, bus bar to lead, or end studs; available space | Decides between DNX and DNXC and the hardware that comes with it. |
| Blown fuse indicator required or not | DENCO's C-rated fuses are offered with or without one. |
| Protection study, coordination requirements and the capacitor's case rupture curve, if available | Lets DENCO check the proposed rating against the curves you are coordinating with. |
| Test requirements, including third-party testing | DENCO tests in house and can arrange third-party testing at IPH Berlin on request. |
| Quantity, spares and required date | DENCO's lead time is 30 days on all products. Custom designs are scoped separately. |
The electrical data in more detail
Capacitor current is the base of every sizing method. For a single-phase unit it is the unit kvar divided by the unit kV; the USDA Rural Utilities Service bulletin gives the example that each 100 kvar capacitor draws 13.9 A on a 7.2 kV system. Fuses are then applied with a continuous current margin. One manufacturer's capacitor fuse selection guide calls this the fusing factor and puts it typically in the range of 1.3 to 1.65 per unit, to cover kvar tolerance, harmonics and continuous overvoltage. Application guides for full-range current-limiting capacitor fuses use 1.35, and other published guidance runs to 1.65 or 2 times for low-voltage and IEC-market fuses.
Because those figures are practices of particular manufacturers and regions, not a standard, DENCO asks for the raw data rather than a target amp rating. If you have done your own calculation, send it with the inputs behind it.
Voltage matters twice. The unit voltage sets the fuse voltage class, and any operation above nameplate voltage raises the current: one manufacturer's formula sheet gives actual kvar as rated kvar times the square of actual over rated voltage. Tell DENCO if the bank runs at a voltage different from the unit rating.
Bank connection, fault current and stored energy
One manufacturer's selection guide explains that in ungrounded or multi-series-group banks, faults are limited by the capacitors, with fault current typically less than 2 or 3 times the bank load current, while in single series group grounded wye or delta banks the fault current is limited only by the available system fault current. The first case asks the fuse to clear low currents; the second asks it to interrupt high ones.
Parallel units matter for energy. When a unit fails, the energy stored in its series group is available to dump into the failed unit and its fuse. The same guide calculates that energy at 3.19 joules per kvar, from the parallel capacitance charged to 1.1 times the crest of rated voltage. For a group of 12 units of 200 kvar, the 11 healthy units hold about 11 x 200 x 3.19 = 7,018 joules. Adjacent banks on a common bus add to it, as a regional transmission organization's capacitor guideline points out.
Telling DENCO how many units are in parallel, and whether other banks share the bus, lets that energy be checked against the fuse and against the capacitor's case rupture limits.
Switching and harmonics
Back-to-back switching produces high-frequency inrush. One switchgear manufacturer's technical FAQ puts the frequency for back-to-back banks in the range of 2 kHz to 30 kHz, depending on the banks' size and configuration and on any limiting impedance. If the bank has inrush or outrush reactors, include their values. A university design standard in this guide's sources asks bank submittals to state peak inrush, rms inrush, inrush frequency and duration, which is the same information a fuse reviewer wants.
For harmonic filter banks, send the tuning and the expected harmonic currents. For plain power factor correction banks in plants with large drive or rectifier loads, send the supply transformer kVA and impedance and the available short-circuit kVA: one manufacturer's plant guide estimates the parallel resonance order as the square root of system short-circuit kVA divided by bank kvar, and a resonance near a characteristic harmonic changes the fuse duty. If you only have a power quality survey, send that.
Mechanical and environmental details
The DNX is clip style, with threaded end studs available. The DNXC mounts from a bus bar to the capacitor lead. Photos of the existing mounting and a note of the clearances answer most mechanical questions at once.
If the enclosure is new or being rearranged, say so and give the space available per fuse. The DNX body diameter printed in the DENCO catalog is a maximum, and DNX and DNXC dimensions should be confirmed with DENCO before the layout is fixed. If the bank's inspection routine relies on seeing which fuse has operated, ask for a blown fuse indicator; DENCO's C-rated fuses are offered with or without one.
Give the maximum ambient the fuse will see inside the enclosure, not the outdoor design temperature. The DNXC derating in the DENCO catalog is AT = A25 [1 - 0.0065 (T - 25)], based on the maximum ambient the fuse will see, so a 45 A DNXC carries the equivalent of 36.2 A at 55 °C. One capacitor maker's manual for metal-enclosed banks recommends shading where daytime temperatures exceed 40 °C and has fans start at about 85 °F, which shows how warm these enclosures are expected to run.
Example: a complete request
The request below would let DENCO engineering propose a rating without a round of questions. The figures are illustrative.
- Application: new metal-enclosed power factor correction bank, 13.8 kV, ungrounded wye, one series group, 7960 V 200 kvar units, 3 units per phase.
- Unit current: 200 / 7.96 = 25.1 A per unit; our calculation used a 1.35 margin, 33.9 A at 25 °C.
- Fault current at the bank: 18 kA symmetrical, X/R 12, from the attached study.
- Switching: single bank, vacuum switch, inrush reactor 50 microhenries per phase, no other banks on the bus.
- Harmonics: drive load about 10% of transformer capacity; power quality survey attached.
- Enclosure: maximum internal ambient 50 °C; bus bar to lead mounting preferred; blown fuse indicator required.
- Attached: capacitor data sheet with case rupture curve, single-line drawing, protection study reference.
- Commercial: 9 fuses plus 3 spares, required on site in 6 weeks, no third-party testing.
Common mistakes in capacitor fuse RFQs
These are the gaps that most often delay a quote.
- Sending only a target amp rating, without the capacitor voltage, kvar and connection behind it.
- Giving system voltage but not the unit voltage, which leaves the fuse voltage class open.
- Quoting fault current without saying whether it is symmetrical or asymmetrical.
- Giving outdoor air temperature instead of the maximum temperature inside the enclosure.
- Leaving out adjacent banks on the same bus, which add parallel energy and back-to-back inrush.
- Sending a part number typed from memory instead of a photo of the label.
What DENCO sends back
With a complete request, the reply is a proposal rather than a questionnaire. Expect the proposed series and rating, or a note that the catalog does not cover the duty and a custom design is needed. Where a DNXC is proposed in a warm enclosure, the reply should show the derated rating against your calculated minimum, so you can see the margin.
Ask for the time-current curve of the proposed rating if you need to plot it against the capacitor's case rupture curve or upstream devices. DNXC curves are on DENCO catalog p.73; for DNX ratings, ask for the curve that matches the C number proposed.
Commercial terms follow the same request: quantity, spares, the 30-day lead time DENCO quotes on all products, and any custom design or third-party testing scope. If something in the proposal does not match your study, reply with the study page; DENCO engineering can work directly with the engineer who signs it off.
How to send it
Use the quote form on the contact page, or call DENCO at 1-800-305-FUSE (3873) or (305) 273-6226. Attach drawings, nameplate photos and studies to the request. If the data is incomplete, send what you have and say what is missing; DENCO engineering will ask for the rest.
Frequently asked questions
Can DENCO quote from a fuse part number alone?
A part number is a good start, especially with photos. For a replacement in an existing bank, add the capacitor unit voltage and kvar and the enclosure ambient so DENCO engineering can confirm the replacement against the application, not only the label.
Do I need a protection study before asking for a quote?
No, but say whether one exists. A quote can be prepared from the bank data, and the final fuse choice should still be confirmed against the capacitor manufacturer's data and a protection study for the bank.
Should I send the fuse rating I calculated?
Send it, and send the inputs behind it. Sizing margins differ by manufacturer and region, so the unit voltage, kvar, harmonics and ambient let DENCO check the calculation instead of relying on the result.
How long does a capacitor fuse order take?
DENCO quotes a 30-day lead time on all products. Custom designs and requested third-party testing are scoped with the quote.
What if I do not know the available fault current?
Say so, and send the system voltage, transformer size and impedance if you have them. The fault level affects the interrupting rating check and whether the bank's faults are limited by the capacitors or by the system.
Why does DENCO ask how many capacitors are in parallel?
When one unit fails, the healthy units in its group discharge into it through its fuse. One manufacturer's method puts that stored energy at about 3.19 joules per kvar, so the count of parallel units sets the energy the fuse and failed unit must absorb.
Can I send a nameplate photo instead of typing the data?
Yes. Nameplate and fuse label photos are often better than typed data, because they show the unit voltage, kvar, frequency and manufacturer exactly as marked.
Can one RFQ cover several banks with different capacitors?
Yes. List each bank separately with its unit voltage, kvar, connection, units in parallel and enclosure ambient, and give the quantity per bank. Fuses for different unit ratings are usually different parts, even in the same substation or plant.
Next step
Limits of this article
- This checklist supports a quotation request. It is not a fuse selection or a coordination study. Confirm the final fuse against the capacitor manufacturer's data, the case rupture curve and a protection study for the bank.
- The worked figures and the example request are illustrative. Confirm with the capacitor maker's data and a protection study before applying any result.
- Capacitors hold a charge after disconnection. Disconnect, wait, short circuit and ground the units as OSHA 29 CFR 1910.269(w)(1) requires, and follow NFPA 70E, before taking nameplate photos or handling fuses inside an enclosure.
- DENCO's family-level specifications are pending technical review by DENCO.
Related
- How to Size a Capacitor Fuse
- Capacitor Fuse Interrupting Rating and Parallel Stored Energy
- DNXC Selection by Capacitor kvar and Unit Voltage
- Replacing an Obsolete or Hard-to-Get Capacitor Fuse
- DNX and DNXC current-limiting capacitor fuses
- C-rated capacitor fuses
- DNX vs DNXC: Which DENCO Capacitor Fuse Fits?
- How to Read a DNX or DNXC Catalog Number
- Replacing Blown Capacitor Fuses Safely
- All capacitor fuse guides
Sources
- USDA Rural Utilities Service Bulletin 1724D-112, The Application of Capacitors on Rural Electric Systems
- Capacitor fuses, Technical selection guide, 1VAG38852-TG Rev A (2024), manufacturer application guide
- PJM TSS guideline V.G, PJM Design and Application of Shunt Capacitors (2017)
- Technical FAQ FA336633, back-to-back capacitor bank breaking current, switchgear manufacturer
- Texas A&M Facilities Design Standard, Capacitor Bank
- Power factor correction: a guide for the plant engineer, SA02607001E (2024), manufacturer guide
- MV automatic power factor correction capacitor banks, IB158008EN (2015), manufacturer manual
- DENCO Fuses catalog, C-rated capacitor protection fuses (p.59) and DNX/DNXC (pp.72 to 74)
- OSHA 29 CFR 1910.269(w)(1)
- NFPA 70E, Standard for Electrical Safety in the Workplace