Capacitor fuse guide · Specify and buy
Buying Capacitor Fuses: Lead Time, Custom Builds and Testing
DENCO Fuses quotes a 30-day lead time on all products, including its DNX and DNXC capacitor fuses. It takes OEM and specialty custom design work, tests in its own factory lab, and arranges third-party testing at IPH Berlin on client request. Its fuses are manufactured in an ISO 9001:2015 certified facility.
Key points
- Lead time: 30 days on all DENCO products. Plan spares around it rather than assuming stock.
- Catalog coverage: DNX 2.8 to 38 kV, 1C to 140C; DNXC 8.3 to 23 kV, 10 to 65 A; Types 1 to 9 from 1 kV to 5.5 kV.
- Custom designs: DENCO takes OEM and specialty custom work, and its Types 1 to 9 catalog pages note fuses can be designed to customer specifications.
- Testing: in-house at DENCO's factory lab; third-party testing at IPH Berlin on client request.
- Quality wording: fuses are manufactured in an ISO 9001:2015 certified facility. Quote that wording, not a certification claim.
Who you are buying from
DENCO Fuses, Inc. is based in Miami, Florida. It was incorporated in Florida in 1988 as DenMar Transit Engineering, later DenMar Fuses. The team has over 100 years of combined experience, solely in manufacturing electrical fuses.
DENCO serves utilities and power companies, OEMs and specialty custom design customers, electrical contractors and transit. Its C-rated capacitor fuse family covers capacitor and capacitor bank protection, power factor correction equipment, harmonic filtering equipment, induction heating systems, and high power drives and welders, for use indoors or outdoors within an enclosure. The family is current-limiting with silent operation and no discharge, and is offered with or without a blown fuse indicator.
For a buyer, the practical points are what DENCO can take on and how to reach the people who answer technical questions: catalog capacitor fuses from 1 kV to 38 kV, custom designs for OEM and specialty work, in-house testing, and third-party testing on request. The sections below take each in turn, then cover spares, purchase order wording and the mistakes that slow orders down.
What the catalog covers
Before asking for a custom build, check whether a catalog series already fits. The table summarizes DENCO's capacitor fuse series as printed in the catalog. Ratings outside these rows, or a mounting the catalog does not show, are the starting point for a custom request.
| Series | Voltage | Current | Interrupting rating | Mounting and notes |
|---|---|---|---|---|
| Types 1 to 9 | 1 kV to 5.5 kV | 25 to 200 A at 1 to 2.5 kV; 50 to 175 A at 3 kV; 6 to 100 A at 4.3 kV; 6 to 75 A at 5.5 kV | 40 to 65 kA symmetrical, rising with voltage | Catalogued by maximum AC voltage and Type number; can be designed to customer specifications |
| DNX | 2.8 kV to 38 kV | 1C to 140C | 50 kA asymmetrical | Clip style; threaded end studs also available |
| DNXC | 8.3, 15.5 and 23 kV | 10 to 65 A | 50 kA | Full-range; bus bar to lead; derated above 25 °C |
Lead time and planning
DENCO quotes a 30-day lead time on all products. Lead times for medium voltage fuses are commonly longer, which matters most when a bank is running on its contingency margin with fuses out, or when an OEM build is waiting on one line item.
Plan around the 30 days rather than assuming stock. The cost of waiting is easiest to see from the bank side. A relay maker's unbalance paper gives the voltage rise on healthy units in a grounded wye, externally fused bank after F units in one group are lost as S x P / (S x P - F x (S - 1)). With 3 series groups of 8 units, one open fuse puts the healthy units in that group at 24 / (24 - 2) = 1.091 times their normal voltage. A second open fuse in the same group gives 24 / 20 = 1.20, above the 110% contingency figure IEEE's capacitor subcommittee described for IEEE 18-2002 units. A bank in that state usually trips, and stays out until fuses arrive.
If the request is a custom design, the schedule is set during quoting, so say when you need the fuses.
Planning spares: a worked inventory
No standard sets a spares quantity for capacitor fuses; it is the owner's decision. What helps is a clear count of positions by rating, because a substation or plant often uses several ratings that look alike. The example below is illustrative.
Take a site with two banks. Bank 1 is a 12.47 kV grounded wye bank of 7200 V, 200 kvar units, 4 per phase, in an enclosure that reaches 40 °C. Bank 2 is a 24.94 kV grounded wye bank of 14400 V, 300 kvar units, 3 per phase, outdoors at a 40 °C maximum. Working through the DNXC selection by kvar method in this guide, Bank 1 lands on DNXC8-45 (27.8 A unit current, 37.5 A minimum, 45 x 0.9025 = 40.6 A) and Bank 2 on DNXC15-35 (20.8 A, 28.1 A minimum, 35 x 0.9025 = 31.6 A). That is 12 positions of one part and 9 of another, so spares have to be held for both. Both results are calculated starting points that DENCO and the bank's protection engineer still confirm.
Order the spares with the first lot so they come from the same build and paperwork. Store them as the fuse maker advises: one fuse maker's instructions call for a clean, dry storage area and an inspection for damage and missing parts on receipt.
Custom designs
Not every bank fits a catalog row. A voltage class, current rating, mounting or end connection that the catalog does not list can be reviewed as a custom build. DENCO's catalog pages for its 1 kV to 5.5 kV capacitor protection fuses (Types 1 to 9) note that they can be designed to customer specifications, and the DNX catalog notes threaded end studs as an alternative to clip ends.
For a custom request, send the same application data you would for a catalog part, plus what the listed parts do not meet: physical envelope, terminal style, rating, or test requirement. Common triggers are a calculated DNXC requirement above the top rating in a class (65 A at 8.3 kV, 43 A at 15.5 kV, 25 A at 23 kV), a bank with an unusual unit voltage, or an existing enclosure whose clips or bus spacing no current part fits.
Testing
DENCO tests fuses in house at its factory lab. When a project requires independent results, DENCO can arrange third-party testing at IPH Berlin in Germany on client request. Say so in the RFQ, with the test standard and the tests you need, so the testing is scoped into the quote and schedule.
For the DNXC series, the DENCO catalog states the fuses were tested at IPH to IEC 60282-1: 2009-10 and IEC 60282-2: 2008-04. That is the catalog's own wording. For other ratings or for test reports, ask DENCO what exists and what would need to be run.
Routine production testing is a separate question from design testing. One fuse maker describes pulsing each current-limiting fuse twice with a pulse calibrated to 95% of its published minimum melt I2t, and notes that a resistance check alone cannot find a damaged element. If your specification needs routine test records for each fuse, say so in the RFQ and ask DENCO what its factory lab performs and documents.
It helps to name the right standard. IEC 60282-1 covers high-voltage current-limiting fuses, and IEC 60549 covers fuses for the external protection of shunt capacitors, with capacitor fuse-links expected to meet IEC 60282-1 plus the additional tests of IEC 60549. In North America, IEEE C37.41 sets design tests for high-voltage fuses, including interrupting, temperature-rise and time-current tests. Write the edition you need into the purchase order.
Quality system wording
DENCO fuses are manufactured in an ISO 9001:2015 certified facility. If your supplier qualification form asks for quality system details, ask DENCO for the documents your form requires.
For capacitor fuses in the Types 1 to 9 series, the catalog states they are designed to ANSI C37-41 specs. That is the catalog's wording, not a listing or certification claim.
Replacement orders vs new designs
A replacement order for an existing bank and a specification for new equipment need different information, and it helps to say which one you are sending.
For a replacement, the most useful items are the existing part number exactly as marked, photos of the fuse label and mounting, the capacitor nameplate, and the number of positions. DENCO engineering will confirm a replacement from that data. No cross-reference is assumed from a part number alone.
For new equipment, start from the bank design: capacitor unit voltage and kvar, connection and grounding, units in parallel, available fault current, harmonic and switching duty, enclosure ambient and the mounting you intend to use. In both cases, name the person who signs off the protection study, so DENCO engineering can work directly with that engineer on curves and ratings.
Writing the purchase order
A capacitor fuse purchase order that names the application as well as the part avoids most disputes at receipt. The items below are a practical minimum; your own procurement rules may add more.
Where the order is for a replacement in a bank with a history of fuse operations, add a note of the cause found, so the supplier knows whether the duty has changed since the original fuses were chosen.
- Full catalog number for each position, with the exact C number for any DNX row.
- Capacitor unit voltage and kvar the fuse is for, and the maximum enclosure ambient used in sizing.
- Interrupting rating required and its basis, symmetrical or asymmetrical.
- Mounting style and end connections, and whether a blown fuse indicator is required.
- Quantity per rating, spares, and the delivery date.
- Any test standard, edition and witness or third-party testing requirement.
- Documents required at shipment, such as curves or test records, agreed during quoting.
Common mistakes when buying capacitor fuses
These cost the most time after the order is placed.
- Ordering exact quantities with no spares, then waiting a full lead time after the first failure.
- Writing "ISO certified" or a listing claim into a specification from a catalog phrase. Quote the catalog wording as written.
- Asking for third-party testing after the order instead of in the RFQ.
- Treating two ratings that look alike as one stock item across banks.
- Specifying a superseded standard edition from an old drawing without checking the current one.
- Leaving the enclosure ambient off a DNXC order, so the rating is chosen for 25 °C.
Frequently asked questions
What is DENCO's lead time on capacitor fuses?
DENCO quotes a 30-day lead time on all products, including capacitor fuses. Custom designs and requested third-party testing are scheduled during quoting.
Can DENCO build a capacitor fuse that is not in the catalog?
DENCO takes OEM and specialty custom design work, and its capacitor fuse catalog pages note fuses can be designed to customer specifications. Send the application data and what the listed parts do not meet.
Can I get independent test results for capacitor fuses?
Yes, on request. DENCO tests in its own factory lab and can arrange third-party testing at IPH Berlin. Include the standard and tests you need in the RFQ.
Is DENCO ISO 9001 certified?
The accurate statement is that DENCO fuses are manufactured in an ISO 9001:2015 certified facility. Ask DENCO for the documentation your supplier qualification requires.
How many spare capacitor fuses should I keep?
No standard sets a number; it is the owner's decision. Count positions by exact rating, allow for the 30-day lead time, and order spares with the first lot so they match.
Who makes capacitor fuses for OEM metal-enclosed banks?
DENCO supplies OEMs and specialty custom design customers. For a new enclosure, send the unit data, ambient and mounting, and DENCO engineering will propose DNX, DNXC or Types 1 to 9 parts, or a custom design.
How do I reach DENCO for a capacitor fuse quote?
Use the quote form on the contact page, or call 1-800-305-FUSE (3873) or (305) 273-6226. Attach nameplate photos, drawings and any protection study to the request.
Does DENCO supply fuses for transit and induction heating capacitors as well as utility banks?
DENCO serves transit, and its C-rated capacitor fuse family lists induction heating systems and high power drives and welders among its applications, alongside capacitor bank, power factor correction and harmonic filter protection. Send the capacitor data for the specific equipment.
Next step
Limits of this article
- This article covers buying and scheduling. It is not a fuse selection or a coordination study. Confirm any fuse against the capacitor manufacturer's data, the case rupture curve and a protection study for the bank.
- The worked inventory and voltage figures are illustrative. Confirm with the capacitor maker's data and a protection study before applying any result.
- Capacitors hold a charge after disconnection. Disconnect, wait, short circuit and ground the units as OSHA 29 CFR 1910.269(w)(1) requires, and follow NFPA 70E, before handling fuses or capacitors.
- DENCO's family-level specifications are pending technical review by DENCO.
Related
- Capacitor Fuse RFQ Checklist: What DENCO Needs to Quote
- DNXC Selection by Capacitor kvar and Unit Voltage
- Capacitor Fuses from 1 kV to 5.5 kV: DENCO Types 1 to 9
- Externally Fused vs Internally Fused vs Fuseless Capacitor Banks
- DNX and DNXC current-limiting capacitor fuses
- Capacitor protection fuses Types 1 to 9
- DNX vs DNXC: Which DENCO Capacitor Fuse Fits?
- How to Read a DNX or DNXC Catalog Number
- Replacing Blown Capacitor Fuses Safely
- All capacitor fuse guides
Sources
- DENCO Fuses catalog, C-rated capacitor protection fuses (pp.59 to 71, 75) and DNX/DNXC (pp.72 to 74)
- IEC 60282-1:2020, High-voltage fuses, Part 1: Current-limiting fuses
- IEC 60282-2:2008, High-voltage fuses, Part 2: Expulsion fuses
- IEC 60549:2013, High-voltage fuses for the external protection of shunt capacitors
- IEEE C37.41-2024, Design Tests and Specifications for High-Voltage (> 1000 V) Fuses and Accessories
- Medium-voltage fuses Technical guide (IEC-oriented), manufacturer guide
- I2t testing for current-limiting fuses, TD132005EN (2015), manufacturer technical note
- IEEE Standards Interpretations for IEEE Std 18-2002 (May 2005)
- Capacitor Bank Unbalance Protection Calculations and Sensitivity Analysis (2022/2023), relay maker's paper
- Current-limiting dropout fuse installation instructions, MN132028EN (2016), fuse maker's instructions
- OSHA 29 CFR 1910.269(w)(1)
- NFPA 70E, Standard for Electrical Safety in the Workplace