Capacitor fuse guide · Choose
Clip-Style vs Bus-Mounted Capacitor Fuses
Clip-style capacitor fuses drop into spring clips on a fuse mounting, so the mounting sets the fit. Bus-mounted fuses bolt between the bank's fuse bus and the capacitor terminal, so the fuse itself forms part of the connection. DENCO's DNX series is clip-style, with threaded end studs available; the DNXC series mounts bus bar to lead.
Key points
- Clip-style fuses fit a mounting; bus-mounted fuses fit the bank's bus bar and capacitor terminals.
- With clip mountings, ferrule size, length, contact spacing and insulation level must match. One manufacturer marks a mounting code on fuse and mount for this reason.
- Mounting does not change the electrical selection, but it decides how many fuses a bank needs, how the operated fuse is found and how hot the connections run.
- Loose fuse connections create hot spots that preload the fuse, and one maker of switching equipment says this is most common on capacitor bank fuses.
- Take fit dimensions from the existing installation and DENCO's drawings, not from another manufacturer's catalog.
Two ways to put a fuse on a capacitor
Capacitor fuses reach the circuit in one of two ways. A clip-style fuse has cylindrical end ferrules that press into spring clips on an insulated mounting, the way many indoor current-limiting fuses mount in switchgear. The mounting is wired to the capacitor terminal and the bus. A bus-mounted fuse has terminals on its end caps that bolt to the bank's bus bar at one end and to the capacitor terminal lead at the other, so the fuse is a structural part of the connection.
In externally fused substation banks, a relay maker's paper describes the arrangement: an individual fuse, externally mounted between the capacitor unit and the capacitor bank fuse bus, typically protects each unit. That is the setting bus-mounted capacitor fuses are built for.
Both approaches appear in DENCO's catalog. The DNX series is listed as clip-style capacitor fuses from 2.8 kV to 38 kV, with threaded end studs also available. The DNXC series is listed for bus bar to lead mounting from 8.3 kV to 23 kV, and the catalog includes a DNXC dimension drawing for that arrangement on p.74.
Clip-style mounting: what has to match
With a clip-style fuse, the fuse and mounting must match on more than voltage and current. One manufacturer's clip-style current-limiting fuse catalog explains that each fuse is marked with a mounting code number, that the code defines the mounting's insulation level, contact spacing and contact type, and that the code on the fuse and the mount must be the same. It also offers extenders to fit a shorter fuse into a longer mounting. That shows what a replacement has to reproduce.
DENCO's catalog lists a maximum body diameter for each DNX size, so check clearances between adjacent fuses and to grounded metal using the maximum, not a nominal figure. Where existing clips are worn, discolored or loose, service or replace them with the fuse; a poor clip contact runs hot.
- Ferrule diameter and overall length
- Clip center-to-center spacing
- Insulation level of the mounting
- Clearance to adjacent phases and grounded metal, using the maximum body diameter
- Whether the mounting needs threaded studs instead of ferrules
Bus bar to lead mounting: what has to match
A bus-mounted fuse replaces a length of conductor, so the fit questions are mechanical and electrical at once: the bolt size and thread at each end, the overall length between the bus bar and the capacitor terminal, and the spacing to the next fuse in the row. Published bus-mounted capacitor fuses are aimed at fusing individual capacitor units in outdoor and enclosed banks, each unit carrying its own fuse from a common bus.
Published manufacturer drawings for bus-mounted capacitor fuses show a recommended minimum spacing between fuses and a specified bolt thread. Spacing is not only a clearance question: one maker rates the parallel-energy capability of its capacitor expulsion fuse tubes for use with the unit spacing recommended per IEEE Std 18-2012. Use DENCO's DNXC drawing for DENCO fuses, and confirm dimensions with DENCO engineering, because extracted DNXC dimensions have not been verified for this guide.
One capacitor fuse maker notes that its fuse type is typically mounted directly on the capacitor, and that its capacitor fuses are non-disconnecting, requiring a separate disconnect switch. Whatever the mounting, a capacitor fuse is not a switch unless its catalog says so.
Single-bushing and two-bushing units
The capacitor itself shapes the mounting. Single-phase units come with one or two bushings. A municipal utility's purchase specification asks for a single bushing with a ground stud for use on its 14.4 kV wye system, or two bushings for use on its 7.2 kV delta system.
Two-bushing units on delta or ungrounded wye systems raise a question the mounting must answer. One capacitor maker's instructions warn that for single-phase two-bushing capacitors fused on only one terminal, and applied on delta or ungrounded wye systems, an internal ground fault from the unfused phase to case might result in case rupture. The same warning covers three-phase capacitors fused on only two terminals. Whether to fuse both terminals is a bank design decision; raise it with the bank designer before choosing hardware.
The mounting's insulation level must suit the unit too. One maker catalogs its units from 2,400 V through 14,400 V at 95 kV BIL, with 125 and 150 kV BIL options at 11,400 to 14,400 V. Clip mountings and bus supports need clearances that match.
Worked example: unit fusing vs group fusing on a 1,200 kvar bank
Mounting style follows the fusing scheme. USDA RUS Bulletin 1724D-112 notes that pole-mounted units are not normally fused individually but by phase, with group fuses in cutouts. Published metal-enclosed designs and externally fused substation banks put a fuse on each unit. One utility's pole bank standard builds a 1,200 kvar bank on its 12,470 V grounded wye system from two 200 kvar, 7.2 kV units per phase.
The comparison uses the published 135% group-fusing figure for grounded wye pole banks and the 1.35 unit-fuse margin from published manufacturer guides, both at 25°C. Unit fusing doubles the fuse count and puts one fuse on every unit, which is what lets the operated fuse identify the failed unit. Group fusing uses the cutouts the pole already needs. Neither choice changes the case rupture and outrush checks, which still apply to each fuse.
| Item | Group fusing (one fuse per phase) | Unit fusing (one fuse per unit) |
|---|---|---|
| Current through each fuse | 400 kvar / 7.2 kV = 55.6 A | 200 kvar / 7.2 kV = 27.8 A |
| Minimum fuse current | 55.6 x 1.35 = 75.0 A | 27.8 x 1.35 = 37.5 A |
| Fuses in the bank | 3 | 6 |
| Typical mounting | Cutout on the crossarm | Bus-mounted between fuse bus and unit terminal |
| DENCO example | Above the DNXC range, which tops out at 65 A | DNXC8, 40 A at 25°C |
Connections, torque and hot spots
A capacitor fuse carries load current continuously, so its connections matter as much as its rating. A maker of switching and protection equipment explains that loose button-head, cap or rod connections create a hot spot that makes a fuse link behave as though it is heavily preloaded, so a transient current that would not normally affect the link causes it to blow unexpectedly. It adds that this is most common on capacitor bank fuses, because their continuous currents are higher.
Torque values come from the equipment documentation. One metal-enclosed bank maker's torque table lists 17 lb-ft for capacitor unit bushing terminals and 20 lb-ft for power fuse terminals. A capacitor maker's instructions say tightening terminal nuts to more than 25 foot-pounds is not required or recommended. Another capacitor maker recommends checking connection torque after the first four weeks and every 24 months after that.
The same documents call for periodic bushing cleaning in contaminated atmospheres to prevent arc-over. Use the torque values the bank and fuse makers publish for your hardware; do not carry a figure from one product to another.
Indication and inspection
Mounting style affects how a blown fuse is found. DENCO's catalog offers its C-rated fuses with or without a blown fuse indicator. Published designs use an indicator button that protrudes when the fuse has operated, or an ejector spring that throws the link's leader out to give a position indication; a relay maker's paper notes that in an externally fused bank the spring-loaded fuse pops out when a failure occurs.
Thermography finds what eyes miss. A test-equipment maker advises energizing the bank for at least an hour before an infrared survey, notes that a blown fuse shows as a temperature difference and that some units have indicators while others do not, and gives twice a year as a typical preventive maintenance interval. A relay maker's paper adds a caution: intact fuses do not necessarily mean the units are healthy, and a failed fuse does not necessarily mean the unit has failed, so capacitance measurement is the full check.
Consider who inspects the bank and from where. An indicator visible from outside the enclosure or from the ground saves a shutdown just to find the operated fuse.
Choosing between clip and bus mounting
In replacement work the existing equipment has usually made the choice: replace like with like and match the fit. In new equipment, the table lists the practical differences. DENCO's catalog lists its C-rated fuses for indoor use, or outdoor use within an enclosure.
Mounting does not change the electrical selection. Voltage class, current rating, interrupting rating and the outrush and case rupture checks are the same whichever way the fuse is held. Settle the electrical rating first, then pick the mounting that fits the equipment, and send DENCO a drawing or photographs of the existing arrangement with the request for quote.
| Consideration | Clip-style (DNX) | Bus bar to lead (DNXC) |
|---|---|---|
| Typical arrangement | Fuse in a separate mounting wired to the unit | Fuse bolted between bus bar and unit terminal |
| What sets the fit | Clips, ferrule size, length, insulation level | Bolt thread, length, spacing on the bus |
| DENCO voltage range | 2.8 kV to 38 kV | 8.3 kV to 23 kV |
| DENCO current range | 1C to 140C | 10A to 65A |
| Interrupting rating as printed | 50kA asymmetrical | 50kA |
| Variants noted in catalog | Threaded end studs also available | Approximate weight listed per part |
Common mistakes
Mounting errors tend to show up months later as hot connections or nuisance operations.
- Matching voltage and current but not ferrule size, length, clip spacing or insulation level.
- Reusing worn or discolored clips with a new fuse.
- Carrying a torque value from one product's manual to another's hardware, or over-tightening capacitor bushings.
- Fusing one terminal of a two-bushing unit on a delta or ungrounded wye bank without the bank designer's review.
- Treating a non-disconnecting capacitor fuse as a means of isolation.
- Taking dimensions from another manufacturer's catalog instead of the installed equipment and DENCO's drawing.
Frequently asked questions
Can I put a clip-style fuse where a bus-mounted fuse was?
Not directly. The two connect differently, and a change means new mounting hardware, new clearances and a check of the ratings. Treat it as an equipment change and have the bank designer review it.
How do I find the right DNX size for an existing clip mounting?
Measure ferrule diameter, overall length and clip spacing, note the voltage and current marked on the old fuse, and send both with the part number to DENCO. DENCO engineering will confirm a replacement and the fit.
Are DNX fuses available with threaded studs?
DENCO's catalog says threaded end studs are also available for the DNX series. State the thread and length you need when requesting a quote.
What torque for capacitor fuse terminals?
Use the value the bank and fuse makers publish for your hardware. As examples, one metal-enclosed bank maker lists 17 lb-ft for capacitor bushing terminals and 20 lb-ft for power fuse terminals, and a capacitor maker says more than 25 foot-pounds on terminal nuts is not recommended.
Do I fuse both bushings of a two-bushing capacitor?
One capacitor maker warns that a two-bushing unit fused on only one terminal, on a delta or ungrounded wye system, can rupture from an internal ground fault from the unfused phase to the case. It is a bank design decision; ask the bank designer.
What spacing do bus-mounted capacitor fuses need?
Follow the fuse maker's drawing. Published drawings show a recommended minimum spacing between fuses, and one maker rates its expulsion fuse tubes' energy capability at the unit spacing recommended per IEEE Std 18-2012. For DNXC, use DENCO's p.74 drawing and confirm with DENCO.
Does a capacitor fuse double as a disconnect?
Not unless its catalog says so. At least one manufacturer states that its capacitor fuses are non-disconnecting and require a separate disconnect switch. Isolate, discharge and ground before touching any capacitor fuse.
Which mounting do metal-enclosed capacitor banks use?
Published metal-enclosed designs fuse each capacitor individually with current-limiting fuses, often with blown-fuse indicators, and the mounting follows the bank maker's layout. For a replacement, match what is installed and send DENCO photographs and the old part number.
Next step
Limits of this article
- This article is general guidance, not a protection study. Confirm every fuse selection, and the worked example here, with the capacitor maker's data and a protection study by a qualified engineer.
- Capacitors hold a charge after they are disconnected. Before handling fuses or units, disconnect, wait, short circuit and ground as OSHA 29 CFR 1910.269(w)(1) requires, and follow NFPA 70E, Standard for Electrical Safety in the Workplace.
- DNX and DNXC dimensions are not given here because the extracted catalog figures have not been verified. Use DENCO's drawings and confirm with DENCO engineering.
- Mounting details and torque values quoted from other manufacturers describe their products only and do not imply interchangeability with DENCO fuses.
- DENCO ratings quoted here are from DENCO's catalog and are pending technical review. Confirm current part numbers and ratings with DENCO engineering before ordering.
Related
- Fusing Metal-Enclosed Capacitor Banks
- Fusing Pole-Mounted Capacitor Banks
- Inspecting and Maintaining Capacitor Fuses: Indicators, Thermography, Testing and Safety
- Replacing Blown Capacitor Fuses Safely
- DNX and DNXC capacitor fuses
- C-rated capacitor fuses
- How to Size a Capacitor Fuse
- Capacitor Fuse Voltage Rating: Unit Voltage, System Voltage and Connection
- Capacitor Fuse Interrupting Rating and Parallel Stored Energy
- All capacitor fuse guides
Sources
- DENCO Fuses catalog, C-rated capacitor protection fuses, pp.59-75 (DNX / DNXC pp.72-74)
- Eaton Cooper Power series, NX indoor current-limiting fuses, Catalog Data CA132049EN (2020)
- Eaton Cooper Power series, NXC full-range current-limiting capacitor fuse, Catalog Data CA132047EN (2019)
- Eaton CA132034EN, Capacitor expulsion fuse (2023)
- Eaton CA230003EN, MV single-phase unfused capacitor units (2021)
- Eaton IB158008EN, AutoVAR MV automatic PFC capacitor banks (2015)
- Eaton TD230005EN, Group capacitor fusing for pole-mounted capacitor banks (2017)
- Mersen, Medium Voltage catalog (2024), capacitor fuses pp.43-50
- GE, Instructions GEH-2743B, AC Power Capacitors
- Brunello, Kasztenny, Wester, Shunt Capacitor Bank Fundamentals and Protection (GE Multilin, 2003)
- S&C GridTalk, Some Tips to Avoid Many Nuisance Fuse Operations (2017)
- Vishay Doc 13193, Assembly and Maintenance Instructions for AC and DC Power Capacitors (2019)
- Fluke, Troubleshooting power factor correction capacitors (2013)
- Moxley, Pope, Allen, Capacitor Bank Protection for Simple and Complex Configurations (SEL, 2012)
- Dhillon, Tziouvaras, Protection of Fuseless Capacitor Banks Using Digital Relays (PG&E / SEL, 1999)
- ABB Power T&D, Capacitor Fuses Selection Guide, TD 38-852 (1999)
- USDA Rural Utilities Service, Bulletin 1724D-112, The Application of Capacitors on Rural Electric Systems
- Snohomish County PUD material standard 646060.1, Pre-Assembled Pole Mounted Fixed Line Shunt Capacitor Bank (2012)
- City of Columbus, TDMIS-9122 Individual Capacitor Units (2022)
- City of Columbus Division of Power, TDMIS 2700 Protection (2022)